Description
Technical Data
Approvals : IS 694 marked, FIA/TAC
Voltage Grade : Up to and including 1100V
Conductor : Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility. The strands are twisted with high precision to impart circularity for the conductor.
Insulation : Specially formulated flame retardant PVC insulation is used. The FR property retards the propagation of flame without compromising safety.
Insulation Conformity : IS 5831, Type A/D FR 70oC
Colours : Red, yellow, blue, black, green, grey & white
Marking : The cables are printed with marking of ‘SUPEREX FR’ from 1 Sq. mm to 4 Sq. mm & “RR KABEL FR” for all other sizes.
Packing : 90 mtr. coil is packed in protective cartons upto size 6 Sq. mm. Project packing of 180 mtr. also available.
Cable Design Parameters
Please complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – grey, 07 – white.
Part Number | Nominal Cross Sectional Area(sq.mm) | Nominal Insulation thickness (mm) | Number *Nominal Dia. Of Strands | Approx Overall Diameter (mm) | Max. DC Conductor Resistance of 20°C (Ω/km) | Current Rating (Amps) | |
Casing | Concealed | ||||||
01010102xx20 | 0.75** | 0.6 | 24/0.2 | 2.3 | 26.0 | 9 | 8 |
01010103xx20 | 1 | 0.7 | 14/0.3 | 2.7 | 18.1 | 14 | 13 |
01010104xx20 | 1.5 | 0.7 | 22/0.3 | 3.0 | 12.1 | 18 | 16 |
01010105xx20 | 2.5 | 0.8 | 36/0.3 | 3.7 | 7.41 | 24 | 20 |
01010106xx20 | 4** | 0.8 | 56/0.3 | 4.1 | 4.95 | 30 | 26 |
01010107xx20 | 6** | 0.8 | 84/0.3 | 4.6 | 3.30 | 38 | 33 |
01010108xx20 | 10** | 1.0 | 140/0.3 | 7.0 | 1.91 | 52 | 45 |
01010109xx20 | 16** | 1.0 | 126/0.4 | 8.1 | 1.21 | 70 | 60 |
*Conductor as per IS 8130
** Insulation Type D as per IS 5831
Test | Test Method | Values |
Limited Oxygen Index | IS 10810 P-58 | >29% |
Limited Temp. Index | IS 10810 P-64 | >250 °C |
Reviews